fischer installation-systems main-catalogue Page 454
Commercial customer offer**Top sellers from Fischer
Foam Barrier System PLUS · Fire protection system FireStop Application data - UL Blank Opening Metallic Pipes and Conduits Cables / Cable Trays Insulated Metal Pipes Mixed Penetrations Max. possible sizes of penetrants Max 32 in. x 32 in. (813 x 813 mm) Max 8 in. (203 mm) diameter Max 24 in. (610 mm) wide by max 6 in. (152 mm) deep cable tray Max 8 in. (203 mm) diameter with 1 in. (25 mm) insulation See listed system Barrier System PLUS UL C-AJ-0158, W-L-0052 C-AJ-1669 C-AJ-3341; C-AJ-4110; W-L-4091 C-AJ-5383 C-AJ-8260; C-AJ-8261 9 454
500 Pages | Valid until 12/2025 | Previous page | Next page
Choose your language
Legal issues
The manufacturer is exclusively responsible for the content, price and article details of the products and offers presented in the catalogues. Subject to technical and optical changes by the manufacturer and errors excepted.